Type |
Cooling Tower Model |
|
|
|
|
|
|
|
|
Standard Design Conditions |
Cooling Capacity (ct) |
150 |
200 |
250 |
300 |
350 |
400 |
450 |
500 |
Heat Load (kcal/h) |
585000 |
780000 |
975000 |
1170000 |
1365000 |
1560000 |
1755000 |
1950000 |
Circulating Water (㎡/h) |
117 |
156 |
195 |
234 |
273 |
312 |
351 |
390 |
Temperature at Inlet of Cooling Tower (℃) |
37 |
Temperature at Outlet of Cooling Tower (℃) |
32 |
Temperature at Outlet of Cooling Tower (℃) |
27 |
Temperature at Outlet of Cooling Tower (℃) |
Length (mm) |
1790 |
2100 |
2360 |
2800 |
Width (mm) |
3960 |
4370 |
4800 |
5830 |
Height of Deck (mm) |
2610 |
2840 |
2855 |
3155 |
Height of Deck (mm) |
3060 |
3290 |
3305 |
3605 |
Materials of Major Parts of Cooling Tower |
Fan Cylinder |
FRP |
Fan Deck |
FRP |
Casing |
FRP |
Top Water Tank |
FRP |
Bottom Water Tank |
FRP |
Filler |
PVC |
Structure |
SS400+HDG |
Fan Wing / Fan Hub |
ALUMINUMALLOY |
Operating Part of Cooling Tower |
Fan and Pulley |
Fan and Pulley |
1500 |
1700 |
2000 |
2000 |
2400 |
2400 |
2400 |
2400 |
Fan and Pulley |
972 |
1470 |
1650 |
1950 |
2214 |
2436 |
2568 |
2766 |
How to Supply Power |
V-Belt |
Specifications of Pulley at Motor |
502B |
5V5 02 |
5V5 02 |
5V5 03 |
5V5 03 |
5V5 03 |
5V5 03 |
5V5 53 |
Specifications of Pulley at Fan |
1602B |
5V1 702 |
5V1 802 |
5V1 803 |
5V1 803 |
5V2 103 |
5V2 103 |
5V2 103 |
Belt Specifications |
BP75 |
5VX850 |
5VX900 |
5VX900 |
5VX900 |
5VX1060 |
5VX1060 |
5VX1060 |
Fan Revolution |
521.0 |
489.0 |
461.8 |
464.4 |
464.4/td>
| 398.1 |
398.1 |
437.9 |
Motor |
Rated Capacity (kw) |
3.7 |
7.5 |
7.5 |
11 |
15 |
15 |
15 |
18.5 |
Type |
Totally enclosed, insulation grade F, protection grade IP54 |
Power |
3PH / 60HZ / 220V (380V / 440V) |
Diameters of Pipes and Nozzles |
Water Inlet Pipe |
100A x 2 |
125A x 2 |
150A x 2 |
200A x 2 |
Water Outlet Pipe |
125A x 1 |
200A x 1 |
250A x 1 |
Discharge Pipe |
80A X 1 |
Excess Water Pipe |
65A X 1 |
80A X 1 |
100A X 1 |
Supplementary Water Pipe |
32A x 2 |
50A x 2 |
Cooling Water Inlet/Outlet Pipe Flange |
KS 10K, FF Type |
Cooling Water Loss |
Loss to Vaporization (%) |
0.74 |
Loss to Drift (%) |
Less than 0.005% of circulated water |
Weight |
Weight during Transport (kg) |
1200 |
1500 |
1600 |
1800 |
2100 |
2220 |
2350 |
2400 |
Weight during Transport (kg) |
2790 |
3120 |
3550 |
3950 |
4600 |
5530 |
5800 |
6000 |