고객지원

  • 고객 10대 서비스
  • 일반 기술자료
  • 냉각탑 열 성능시험
  • Q&A

전문 기술자료 대한민국 냉각탑 건설/설계 선도 전문업체 대일아쿠아

HOME > 고객지원 > 전문 기술자료


The following procedures are intended to document the conventional methods of measuring airflow. We realize that there are much more highly technical methods available. We also realize that our members have varied needs, some simple, some extremely demanding. This treatise is intended to assist the greatest number of people to be knowledgeable of several current ways to measure the air flow from their fans.

There are two basic methods for air flow testing of cooling towers: Anemometer or Pitot Tube. The purpose of each is to measure the velocity at a point. After a number of points are measured to obtain a representative or average velocity, the total airflow is calculated using the net discharge area of the fan. Each of these methods is discussed below.

1) Anemometer Method

The anemometer is basically a calibrated propeller. As the air turns the propeller, its speed of rotation is counted mechanically or electrically measured by a D.C. motor.

(1) The oldest design is a vane anemometer, which has a mechanical readout of feet per minute velocity of air which passes through the anemometer over a period of time, usually a 30 second interval. In use, the anemometer is held in the air stream on a pole at the prescribed spot. A timer calls "start", and the operator pulls a string to start the anemometer. At 30 seconds, the timer calls "stop". The operator retrieves the anemometer, reads the thousands, hundreds and unit counts. He records the reading, resets the counter and moves to the next spot. The readings are later adjusted using a calibration curve and doubled to give a feet per minute reading. As you can see, this instrument is clumsy and takes two skilled people to make repeatable measurements. Note that if a "yaw" measurement was needed, the operator would have to read or estimate and record the yaw angle as well as the counter reading for each spot.

(2) Today there are many electronic direct reading anemometers available although accuracy and moisture resistance varies with cost. A typical instrument displays velocity in ft/min or m/sec and temperature oF or o C. It averages 20 readings over 2 second intervals and can save readings which can be dumped into a standard RS232C interface of a computer. It is battery powered and an extension cord is available.

(3) An upscale version would be a propeller anemometer which has a digital readout based on an analog D.C. voltage proportional to the wind velocity. This is an unshrouded propeller with a tiny generator which can be attached to a pole with a standard 3/4" NPT pipe thread.

2) Pitot Tube Method

The pitot tube measures velocity pressure as the difference between total and static pressure at a point. This pressure is measured with an inclined manometer or an electronic pressure transducer. Temperature must also be measured so the density at each point can be computed. Once density and velocity pressure are measured at a point the velocity can be computed by the formula:

V = 1096.2 x C x (VP/D)1/2
Where,
1096.2 = Unit conversion factor
C = Pitot tube calibration coefficient
VP= Local velocity pressure (inches - H2O)
V= Local velocity (ft/min)
D= Local Air Density (lbm/ft3)

For wet tower a special pitot tube with larger than normal holes in the nose are required. The purpose of the large holes is to prevent water droplets from clogging the tube, causing erroneous readings. There are several types of pitot tubes available, some very sophisticated of high velocity measurements. For the general purposes, velocity pressures will typically be less than 0.5 inches-H2O.

For fan testing in moist air, the Prandtl type design is recommended. However, other types could also be adapted for cooling tower use. A pitot tube developed for cooling tower use should first be calibrated against a well designed pitot tube in a dry air situation. This will allow any correction factors necessary to account for the true performance of the modified tube to be determined.

(1) Pressure Measurement: The velocity pressures which must be measured in a cooling tower application are typically less than 0.5 in-H2O. Impact and static pressures are somewhat higher and can occasionally exceed 1.0 in-H2O. Their pressures fluctuate rapidly due to the turbulence of the flow and the proximity of the measurement to the fan blades. This makes some method of dampening advisable.

Any pressure measurement device suitable to these conditions can be used. A simple inclined manometer is often used. Pressure gauges and electronic pressure transducers have also been used successfully. The pressure measurement device should be checked against a reliable standard before the test and at least once during the test.

When pressure measurement is desired in addition to flow measurement, a system of valves is often used to connect the various pressure signals to the measurement device. These valves can be operated either manually or electrically.

(2) Temperature Measurement: Air temperature should be measured with an electronic temperature sensor attached to the pitot tube. Hand held thermistor types work for this purpose. Air temperature is measured to determine the density of the air. In cases where saturation cannot be assumed, it may be necessary to measure both wet and dry bulb temperature. In these cases, a wetted wick must be provided for the wet bulb sensor.

(3) Barometric Pressure Measurement: Barometric pressure can be measured by any suitable means. Mercury manometers are often used. Electronic absolute pressure transducers have also been used.

(4) Other Apparatus: The pitot tube should be attached to a light aluminum tube with sufficient strength and length to traverse the radius of the fan cylinder. This tube is usually supported by the fan cylinder itself and by a tripod mounted on the fan deck, the pitot tube should be connected to the pressure measurement device by flexible hoses. The temperature sensor must be connected to the output device by a suitable length of wire. The wire and hose should be firmly attached to the aluminum tube to prevent their being entangled in the fan or other cooling tower structure.

3) Where to Measure

Generally there is a precise distance from the edge of the fan ring each of four quadrants of the inlet or discharge area where measurements are taken. A minimum number of points for a fan would be 21, four points in each of five equal area bands plus one point at the center. These points are calculated on the basis of fan diameter and seal disc diameter. These measurements are all in one "plane". Where that plane of measurement is chosen is another problem.

Imagine a fan discharging air. On the inlet side, the air flow is fairly uniform except around beams or other obstacles. On the discharge side the direction is significantly changed and at the center, airflow becomes negative but is blocked by the fans seal disc or hub. The air at the blade tips is still axial but the air vectors near the center of the fan are progressively "bent over" by the effect of the torque applied by the fan blades. At the center of the fan, the air actually wants to reverse direction 180o. This is called the "swirl effect". The net effect would be turbulence close to the center of the fan on the discharge side.

Also, consider if the fan has a short fan ring or a tall velocity recovery stack. The closer the measurement to the fan the less swirl effect is seen. For a tall stack, there is a cone of swirling air which travels at least two fan diameters before all discharge air becomes uniform (axial) again.

Using a pitot tube close to the exit or inlet side of the fan may require drilling four holes approximately 1-1/2" diameter at 90o through the stack for access. Plug the holes with a rubber plug or other means after the test is completed.

(1) Yaw: The fan imparts a horizontal and a vertical component to the air. The angle produced by these two components is the "YAW" angle. The vector resolution of these components yield the actual air velocity. However, to correctly determine the air flow leaving the tower, only the vertical components of the velocity need be measured. This can be accomplished by two methods:

  • ●  Position the anemometer horizontally, therefore only the axial (vertical) component of flow goes through the propeller.
  • ●  Tie a string or streamer onto the anemometer rod. The streamer will show the "local" velocity direction so if you hold the anemometer perpendicular to the streamer it will measure the air velocity in it's "yaw" direction. You then must read the yaw angle from a protractor on the anemometer handle and record it, along with the velocity read. The axial or vertical component will be:

    V A = V yaw x Cos q
    where,
    V A = Axial (vertical) Velocity
    V yaw = Velocity measured in the direction of the yaw angle.
    Cos q = Cosine of yaw angle

    This adds considerably to the time consumed per test but does add a few percent accuracy to the results. This would apply to either an anemometer or pitot tube if measurements are taken on the discharge side of the fan. If you can use a pitot tube on the inlet side of fan (with or without a VR stack) several errors are avoided.
    • ○  Inlet air, close to the plane of the fan is rather uniform - therefore no yaw is present.
    • ○  The confusion of the effect of swirl of yaw at the discharge, at the top of the stack is avoided. The Net Free Area, free of swirl, is well defined. A "caveat" would be that you must not measure within 12 inches of a beam under the fan because of turbulence which would affect the reading. Better to move over into clear air.

(2) Recommended Measurement Locations: First choice (with or without V.R. Stack): In the fan inlet as close as possible to the fan. Second choice (Short Fan Ring): Over the fan with an anemometer or pitot making yaw corrections. Third choice (V.R. Stack): At the top of the stack, making yaw corrections. Net Free Area is considered from the edge of the stack to the edge of the cylinder formed by the seal disc diameter.

Obviously the location you choose will be tempered by the tower configuration being measured, the equipment you have and the time allotted for the test. If you are just comparing two fans, the important thing is consistency. Measure them both exactly the same way. You may or may not choose to measure yaw angles. You may not have pitot equipment. You may not be able to drill four holes in the stack to get under the fan.

Your air flow measurement may not have to be absolute, but you're looking for relative differences in performance between fan A and fan B. All these things can effect your measurement location and method of measurement.


To be continued. Please press the next button....