고객지원

  • 고객 10대 서비스
  • 일반 기술자료
  • 냉각탑 열 성능시험
  • Q&A

전문 기술자료 대한민국 냉각탑 건설/설계 선도 전문업체 대일아쿠아

HOME > 고객지원 > 전문 기술자료


1) Introduction

Much confusion exists in both the cooling tower and the fan industry concerning field testing. There is no doubt that a need exists for a simple, accurate, practical method of evaluating the fan performance since it is a vital factor in overall tower performance. Several fan manufacturers and several tower manufacturers have written procedures, and both CTI in their Bulletin ATP-105 and ASME in their PTC-23 have covered this subject. ASHARE also has a code for small towers. All of these leave something to be desired.

When a cooling tower fails to meet performance guarantees, one of the first items to be investigated is the fan. Truthfully, there are many other factors of equal or greater importance such as water distribution, air distribution, amount of surface and fill, etc. However, the fan flow is something that can be measured after a fashion in the field, and generally is a starting point for remedial work. There is no doubt that this is not an easy task, nor that laboratory accuracy can be maintained, but a reasonable job is possible. Here the statement contained in the former fan test code Bulletin AMCA-110 is subscribed briefly.

"Research undertaken by the members of the Association in cooperation with test code committees of the engineering societies thus far that no accurate or practical method of testing fans in the field has been developed by means of gas analysis or by use of the Pitot tube or other instruments. Since the values obtained from field tests vary so widely from actual results, a guarantee of the performance of fans can be made only from laboratory tests conducted by the manufacturer in accordance with the Standard Test Code for Centrifugal and Axial Fans."

It is true that performance measured in the field should not be used to base fan rating tables, but the industry needs a reasonable method to evaluate fan performance on a tower, and the accuracy can be held to reasonable limits.

2) Instruments

(1) Flow: Most authorities suggest that on an induced draft cooling tower the fan flow shall be measured on the fan discharge side. The instrument to be used should be a calibrated, vane-type anemometer. This type instrument used with a good stop watch is less sensitive to the disturbing factors found in field testing of induced draft towers than other instruments now available. The instrument is accurate at velocities from 200 - 3200 feet per minute which cover the range required.

When the anemometer is held normal to the plane of fan operation, it tends to minimize the errors due to the angle of the air discharged. For example, with an angle of yaw of 14o the anemometer error is only 1%. A table is given under procedure showing corrections for yaw angles up to 50o. In addition, at the velocities found in a cooling fan discharge, the effect of densities other than calibration density (0.075 lb/ft3) are rather low. The following table shows the toleration in density ratio for a 1% variation in a accuracy:

Velocity (ft/min)

Max. value of d/da for 1% error

300

1.05

600

1.10

1200

1.21

1800

1.32

(Note: d is ambient density and da is calibration density.)

An extension rod and a device for starting and stopping the instrument in addition to the stop watch, and two men are a must! One man can use the stop watch and log results while the other handles the anemometer. The other commonly used flow measuring devices are not recommended for tests such as these. The Pitot tube is highly sensitive to yaw angle and in addition, the small static side holes become filled with water very rapidly. The hot wire anemometer is useless in the wet air, as is the velometer. No attempt will be made to go into the characteristics of all these instruments. This does not mean that the anemometer is a perfect instrument as it is slightly affected by water droplets, and by pulsating air flow. It is the best available at this time, and is the instrument to use for this test method.

(2) Static Pressure: The static pressure or resistance pressure under which the flow is produced is very important. The values taken beneath the fan are, of course, negative (lower than atmosphere) and in most cases are all that need to be taken. The pressure readings are very low, generally 0.60" water gauge or less, and for this reason an inclined manometer is suggested. This gauge should have a zero adjustment, a built-in level, a slope of at least 10:1 and 0.01" graduation.

A colored gauge fluid of a density commensurate with the gauge graduations should be used to give direct readings in inches-water gauge. Do not use a water filled U-tube. Remember an error in reading a U-tube of just 1/32" on a 0.40" measurement is an error of about 8% and cannot be tolerated. Together with the manometer you will need a probe to insert through the tower deck. This can be a length of 1/4" tubing with the end smoothed and free from burrs. This coupled with about 40 ft of good neoprene tubing will enable you to leave the gauge standing in one spot while you insert the probe in various locations.

(3) Power Input to Motor: Only those applications where the prime mover is an electric motor are considered here. This will cover about 95% of the towers involved. With an electric motor, the manufacturer? curves for efficiency can be used for the purpose. This means that all we need is to get the power input to the motor. If possible, a three phase wattmeter or two single phase wattmeters can be used. If neither of these is available, then a voltmeter, ammeter, and power factor meter must be used. All meters should have an accuracy of 1% of full scale reading or better. Avoid the mistake of reading only volts and amperes. The power factor changes radically with changes in voltages away from the motor rating, particularly with the new NEMA frame motors. in any case, reading of volts and amperes only is very poor practice and leads to high magnitude of error.

(4) Temperature: Mercury type wet and dry bulb thermometers, with scale divisions no greater than 1 oF should be used.

(5) Fan Speed: It is generally very difficult to measure fan speed directly due to the size of the units and actual physical limitations. It is recommended that the motor shaft speed be measured with a tachometer having an accuracy of 1% or better. Then by using the gear ratio, the fan speed can be calculated. It is possible to use a strobe light except with some older models which do not go low enough in RPM and do not have a good enough light source to make this desirable. Newer models promise to remedy these difficulties, and may prove to be satisfactory. They have an accuracy of 1% of full scale reading.

(6) Barometric Pressure: In most instances, the local power plant or weather station can provide an accurate barometer reading for the test. If this is not available an aneroid barometer, temperature compensated, with scale readings not greater than 0.02" can be used.

(7) Fan Blade Angle: This can be measured at the point on the blade recommended by the manufacturer by using a bubble protractor and a straight edge. Care must be taken to establish any deviation of the fan assembly from level and all blades should be brought to the same location in the cell for measurement.

2)Preliminary Observations

Before we discuss the actual test procedure, it would be well to outline the preliminary observations and precautions that should be taken.

(1) Wind Conditions: The wind direction and velocity should be measured using an anemometer, and noted on the test sheet using a sketch of the cell to show relative direction. The wind is the greater external influence on a test such as this and a test should not be attempted under high wind or gusty conditions. Tests should preferably be run in the early morning or late afternoon when the wind is lowest in velocity and reasonably steady. Good test results cannot be obtained when the wind velocity is greater than 75% of the average fan outlet velocity, and should not be run in any case when the wind exceeds 10 MPH. Also, if the wind shifts direction over 45o during the time of the flow traverse, the test should be voided. If gusts occurs of a magnitude of over 5 MPH greater than the average wind velocity during flow measurement, the test should be avoided.

(2) Fan Inspection: Be sure that the face of the blade is one the leaving air side. This precaution may sound absurd, but you can be assured that some fans have been installed upside-down and running backwards. Check fan tip clearance to be sure it satisfies manufacturer? recommendations. This will not effect the test procedure as such, but if clearances are excessive you will never be able to approach the tunnel test performance of the fan with the field values measured.

Make a sketch of the location of the fan relative to the cell and measure the inside diameter of the fan stack for at least two points 90o apart at the plane of flow measurement. Use the average diameter to calculate the area of the stack. Make sure the eliminator baffles beneath the fan are not clogged or broken. If a guard is placed above the fan it is best to measure the resistance to flow of such a guard, and if it is left in place you will have to estimate the static pressure loss to attribute to it in the final fan analysis.


To be continued. Please press the next button....